4 - DESCRIPTION AND CONFIGURATION OF THE PARAMETERS
Operation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’02
/
Probes
Type
Min. Max. U.o.M. Default Value
1
Presence external air probe
0 = absent
1 = NTC Carel
F 0 1 flag 0
2
Type of humidity/pressure/temperature probe B3
0 = absent
1 = 0-1Vdc or 0-20mA
2 = 4-20mA
F 0 2 flag 0
3
Presence supply air B4
0 = absent
1 = NTC Carel (enable corresponding alarm)
F 0 1 flag 0
4
Value of humidity/pressure at 0 mA, 4mA or 0Vdc
F 0 /5
%rH
bar
0
5
Value of humidity/pressure at 20mA 0r 1Vdc
F /4 100
%rH
bar
100
6
Calibration probe B1
U
-6.0
-10.8
6.0
10.8
°C
°F
0.0
7 Calibration probe B2
U
-6.0
-10.8
6.0
10.8
°C
°F
0.0
8 Calibration probe B3
U -10.0 10.0
%rH
bar
0.0
9
Calibration probe B4
U
-6.0
-10.8
6.0
10.8
°C
°F
0.0
A
Digital filter
U 1 15 - 4
b
Input limit
U 1 15 - 8
c
Unit of measure
0=°C
1=°F
U 0 1 flag 0
9